CDR6i Thermal Overload Relay

Short Description:

The new CDC6i series of electric motor control and protection of series products, using a new generation of technological platform, the application of automatic production and test equipment, really adapt to the real application needs of customers, realize the practical use, quality of the main national products.   This series includes five series of CDC6i ac contactor, CDC6F high current contactor, CDR6i thermal overload relay, CDZ6i contactor type relay, CDP6 circuit breaker motor and their accessories


Product Detail

Product Tags

Feature

  • Over-load Protection
  • Phase Failure Protection
  • Temperature Compensation
  • Manual reset
  • Automatic reset
  • Stop Button
  • Test Button

Specifications

The main technical parameters

Temperature Compensation -10℃~+55℃
Trip Class CDR6i-25、38:10A
CDR6i-93:10
Rated Thermal Current Ui  V 690V
Auxiliary Circuit
Usage Type AC-15 DC-13
Rated Frequency(Hz) 50 50 50
Rated Thermal Current Ui(V) 500 500 500
Rated operating voltage Ue(V) 220 380 220
Rated operating current le (A) 1.64 0.95 0.15
Resistive current lth(A) 5 5 5
Certification CCC、CE

Action Features

No. Mulriple of Setting
Current
Tripping Time Initial Condition Ambient
Temperature
Trip class 10A Trip class 10
Tripping Characteristics for Current Balance
1 1.05 Non-tripping within 2h Non-tripping within 2h Non-tripping within 2h +20°C
2 1.2 Tripping within 2h Tripping within 2h Tripping within 2h
3 1.5 <2min <4min <4min
4 7.2 2s<Tp≤10s 4s<Tp≤10s 4s<Tp≤10s 4s<Tp≤10s
Tripping Characteristics for Current Imbalance
Any 2-Phase, 3rd Phase
1 1.0      0.9 Non-tripping within 2h Non-tripping within 2h Without previous load +20°C
2 1.15      0 Tripping within 2h Tripping within 2h After No.1 Test

Details

CDR6i_detail_0_
CDR6i_detail_1
CDR6i_detail_3
CDR6i_detail_2

  • Previous:
  • Next:

  • Write your message here and send it to us