Product Tags
- High grade PA nylon with high frame retardant shell, high temperature resistance and impact resistance.
- Current-limiting contact system, magnetic blown arc extinguishing device, avoid equipment to withstand large short-circuit current.
- Better arc extinguishing ability to ensure the improvement of breaking capacity.
- Novel appearance and stable performance.
- Clear Contact indication window: position visualization, avoiding incorrect operation.
- Strong environmental adaptability and reliable operation in extreme environment: - 35 ℃ ~ 70 ℃ ambient temperature range.
- High quality, innovative technology, strict testing, lean production and improve efficiency.
Rated voltage |
AC230V(1P), AC400V(2P,3P,4P) |
Rated current |
1A 2A 3A 4A 6A 10A 16A 20A 25A 32A 40A 50A 63A |
Pole |
1P 2P 3P 4P |
Rated insulation voltage |
500V |
Rated impulse voltage |
4KV |
Release type |
Thermo-magnetic |
Tripping curve |
B(3~5In), C(5~10In), D(10~16In) |
Rated breaking capacity |
6000A |
Mechanical life |
20000times |
Electrical life |
10000times |
Standard |
IEC60898-1 |
Use ambient temperature |
-30~+70 |
Accessories |
Auxiliary contact, alarm contact, shunt release, under release,voltage release |